The scariest Techdiver thought,
undetected contamination in the gas we breathe.
A MUST READ for all divers, dive shops
and fill stations, your life can depend on it.
A short introduction:
This is an article extracted from The
Deco Stop posted by swampdiver, a medical doctor, after some research about a
recent incident which occurred to Michael Barnette in June 2004 during a shallow cave dive with
Nitrox 32, where he experienced several acute medical symptoms so bad that he almost
had to be rescued by his dive buddies.
After the dive he reported a smell in his tanks gas
resembling synthetic oil and sent a gas sample to a recognized breathing gas
laboratory. The analysis
came back reporting that the AIR (yes JUST AIR!!! they said!!!) was good and
compliant with the CGA Grade E standard. Not happy with the weird and suspicious results he sent it to
a better lab where they conducted further tests and found traces of
TOLUENE!!!!! in the nitrox mix, apparently from a compressor that
overheated resulting in the break down of the synthetic oil.
TOLUENE is one of the gases produced from that break down.
BIG recommendation, ALWAYS SNIFF YOUR GAS BEFORE YOU
BREATH IT !!!
Here this very good article:
TOLUENE INCIDENT ANALYSIS/DISCUSSION
After spending the last month or so speaking with various physicians,
breathing air lab directors, a carbon supplier, a filter manufacturer, a
couple certified Bauer compressor technicians, a compressor oil
manufacturer, and several people with experience in the field of thermal
and oxidative degradation of oils, I have concluded this toluene episode
likely has quite significant ramifications for the dive industry which
need to be further explored and researched. After speaking with many of
the experts noted above, it appears this incident is not a ‘one-off’
external-source toluene contamination incident, but likely represents a
systemic industry wide problem that presents sporadically only when
certain climatic, compressor, oil, and filtration conditions are met.
What is worrisome about this incident is the potential frequency with
which these conditions likely do occur during the production of
compressed breathing gas particularly in the commercial realm, and the
subsequent risk of serious diver injury and/or death. The technical
diver will always be at the greatest risk from exposure to a volatile
vapor contaminant, and as one toxicologist said after reviewing this
case, “the technical diver may be the ultimate canary in a coal
mine” due to the high partial pressure exposures at depth to these
breathing gas contaminants.
I thought it beneficial to present the knowledge I have gleaned from my
own reading and experience around this interesting case of a non fatal
toluene poisoning as well as pass on what advice the above experts have
offered. It is hoped that by presenting these issues here on TDS to a
well informed global technical dive community that some of the concerns,
and possible remedies might then also filter down to the rest of the
dive industry and community so as to prevent future similar episodes.
Knowledge and safety through education as the saying goes.
This is meant to be an educational discussion and not blame a particular
business as many of these issues discussed will be relevant to most fill
stations. It is apparent that many of the technical issues and risks
illustrated by this case have either been poorly understood to date
within the dive industry, have not been researched adequately, or may
not have been advertised adequately by those involved in the compressed
breathing gas industry who have understood these risks.
It does appear though that there are certain high risk geographic areas
for these problems and Florida because of its climate, particularly at
the time of year this incident occurred, is one of them. Although
Florida is used as an example for incident analysis purposes, other
geographic areas with sustained periods of high temperature and humidity
would also potentially see higher rates of these contamination
incidents.
As there is a fair amount of information to digest I thought it might be
best to break it into sections as follows:
1) Incident data and toluene toxicology
2) Toluene production from thermal (pyrolytic) and oxidative degradation
of compressor lubrication oils: how?
3) Toluene filtration breakthrough: how did it happen?
4) Determining Desiccant Saturation Status
5) Prevention of future incidents and how to assess a fill station’s
potential gas contaminant risk
6) Future research needed
Prior to proceeding if one is unfamiliar with compressor and filtration
design, theory, operation, and maintenance then Ted Green’s article is
the best source of information I have seen to date on many of these
topics. You can find bits and pieces elsewhere, but this is the first
time I have seen this information posted all in one place. Please note
Ted’s important continued emphasis on keeping the compressor cool,
clean, and the filtration dry at all times as this is the key to the
minimization of the risk factors described in this incident. Heat should
become a four-letter word in terms of breathing gas production and
hopefully at the end of this discussion it will be clear or somewhat
clearer as to why. Understanding SCUBA
Compressors and Filtration by Ted Green
1) Incident discussion and toluene toxicity
The second breathing gas analysis revealed Barney’s tank was
contaminated with toluene, a volatile aromatic hydrocarbon similar in
structure to benzene. When one reviews the literature on toluene
toxicology there was significant research done on animal and human
exposures at 1 atm during the 1970’s and 1980’s, but very little
research has been done since this time period despite the 1980’s
literature saying further research into low level exposure was badly
needed. There are no previous cases of divers exposed to toluene that I
could find, and for obvious reasons no research on hyperbaric toluene
exposure has been done. Most of the data on acute exposure comes from
adolescents who ‘sniff’ or ‘huff’ toluene containing substances
such as spray paint, glue, or gasoline (7 percent toluene by weight) in
order to experience a rapid high or euphoria.
In this particular case it is informative to list the symptoms
experienced by Barney and ask the question is toluene responsible for
the diver’s symptoms? I will group them into central nervous system
(CNS) and gastrointestinal (GI) complaints.
CNS Symptoms
-taste alteration described as “rubbery taste”
-feeling odd
-dream-like state
-distinct gaps in memory
-impaired vision and depth perception
-mental capabilities severely impacted with inability to discern
direction of arrows in cave
-confused as to time and place with inability to recall buddy’s name
-no anxiety or panic
-headache
GI Symptoms
-mild nausea
Assessment by Barney post dive: “that was not cool!”
Other important details of note: diver 30 something years old, Nitrox 32
percent, initially diver “blitzed at a rapid pace” according to
buddy, maximum depth 80 ffw (3.5 atm), 30 minute run time, symptoms
resolved quickly on surfacing and with breathing 100 percent O2 at deco
stop for 5 minutes.
Toluene exposure can result from inhalation of the vapor, and ingestion
or skin contact with liquid toluene, a clear colorless volatile liquid
at room temperature. The inhalational route leads to rapid systemic
absorption (just like an anesthetic) with blood toluene levels rising
within ten seconds, and peak blood levels reached about 15 to 30 minutes
after exposure. Toluene and most volatile organic solvents are highly
fat soluble and hence enter the tissues with the highest blood flow such
as the brain, kidney, and liver quickly. Its toxic effects following
inhalation appear rapidly in the CNS and may be enhanced by age, liver
disease, previous acetaminophen (Tylenol) or aspirin ingestion as these
drugs are metabolized by the similar pathways in the liver. Eighty
percent of toluene is metabolized by the liver and the final metabolite
is excreted in the urine. Twenty percent of toluene is eliminated via
the lungs unchanged, and is why one can often smell toluene on the
breath of individuals exposed to the vapor.
Toluene odor is easily detected by the human nose, and depending on what
source one quotes, the odor threshold is 80 ppb, however to actually
recognize the vapor as toluene and not just a generic volatile organic
compound (VOC), a level of up to 8 ppm is quoted. These odor
concentrations are all well below the levels one might see any of the
short term adverse effects at 1 atm. In any case, most noses should be
able to pick up very low concentrations of toluene in the breathing gas
well below what the concentrations the lab will be looking for. The
literature does report that some individuals do have better sensitivity
than others for detecting toluene using smell.
The CNS effects described for acute toluene exposures are very similar
to what Barney experienced as listed above. The experience is similar to
acute alcohol intoxication and several papers describe exposing workers
to alcohol to assess their potential occupational toluene sensitivity.
Like many CNS depressants toluene may initially cause a state of
euphoria with giddiness, but as the concentration increases CNS
depression and narcosis ensues. Physiological effects will depend on the
partial pressure at depth and duration of exposure. Numerous signs and
symptoms of CNS dysfunction are described in the literature including
dizziness, disinhibition, confusion, hallucinations, amnesia, bad taste,
impaired coordination, tinnitus (ringing in ears), decreased manual
dexterity, decreased color discrimination and accuracy in visual
perception, fatigue, and at higher doses tremors, seizures, paralysis,
coma, and death. In one reference from the DOT looking at toluene
exposure (abuse and occupational) and driving risk they concluded
“acute and chronic exposure to toluene can result in severe
impairment.”
In this particular case the swimming “blitz” described at the
beginning of the dive likely increased significantly alveolar
ventilation and pulmonary blood flow delivering a higher dose of toluene
to the brain. This relationship between physical activity (increased
alveolar uptake and higher toluene tissue concentrations) and
enhancement of the toxic effects of toluene can be seen in the figure
below. This enhancement of toxic effects with physical activity would
likely apply to any narcotic vapor contaminant and not just toluene
found in the breathing gas supply. One might speculate on the potential
outcome had this diver been ‘bombing’ a deep wreck to 10 atm with
the same amount of toluene onboard. Having to swim against any current
would have further enhanced the narcosis.
Given that many of these contamination events will present on descent or
shortly thereafter depending on contaminant’s partial pressure,
duration of exposure, and physical activity it would seem prudent for
technical divers to remain close to their buddy on descent so each
other’s physiological status can be monitored closely. A technical
diver’s descent should be considered a high risk time period for the
presentation of potential gas contamination issues.
Although Barney did not experience any respiratory difficulties, toluene
in sufficient concentrations or in sensitive individuals can cause
respiratory distress leading to death. Wheezing from bronchospasm has
been reported quite frequently and in high enough concentrations the
lung’s surfactant layer may be disrupted leading to pulmonary edema
and respiratory failure. If concentrations are high enough direct CNS
suppression of respiration will occur with hypoxia and hypercapnia
followed by death.
Interestingly throughout the literature it has been observed that
toluene sensitizes the heart to circulating catecholamines (epinephrine
and norepinephrine). Several sources mentioned keeping the patient quiet
and immobile for fear of provoking a lethal cardiac arrhythmia with
severe overdoses, sudden movements, and increased myocardial
irritability. Fatal arrhythmias such as ventricular fibrillation have
been observed in animal experiments and conscious toluene overdose
patients, and are thought be due to a direct effect of toluene
sensitizing the heart to circulating catecholamines especially if there
is concurrent strenuous physical activity. It would be quite easy to see
how such a toluene induced cardiac death in a diver, unless gas
contamination was suspected, could be mistaken for a ‘heart attack’
or just be reported as a generic drowning with no antecedent cause
identified.
In summary then Mike’s symptoms are very consistent with a low to
moderate level toluene exposure probably with the toxicity enhanced by
his physical exertion early in the dive. It is possible there were other
minor volatile contaminants involved with this incident, and the
secondary gas analysis done by Analytical Chemists, Inc. of San Diego
may yet reveal these with additional detailed analysis.
2) Toluene Source: Where did it come from?
As mentioned in several of the original posts on this thread one
would have to consider an external source for the toluene contamination
which would have been entrained into the compressor’s intake. I have
heard of one incident where this was the case with a remote intake
located adjacent to a facility with 45 gallon drums of toluene used as
industrial solvent. There are many incidents of BTEX (benzene, toluene,
ethylbenzene, and xylene) contamination from an intake located near a
fuel refilling station especially if the compressor is located in a
marina. This gasoline vapor scenario with BTEX contamination is quite
common in the dive industry and is why one should always check a fill
station’s remote inlet neighbors. Another external source of toluene
could be recently used acrylic paints, glues, or cleaning solvents.
Others familiar with the fill station in question have reported none of
these potential external sources for toluene was an issue.
Prior to this incident I had been aware of some unpublished research
done here in Canada on the subject of high pressure reciprocating
breathing air compressor oil degradation at elevated temperatures which
is what piqued my interest in this case. I mentioned this incident back
in June to one of the persons who had been involved in this research and
he asked to be kept appraised of the situation as it evolved. Once the
contaminant was discovered I called him up and asked, “Guess what was
found in the diver’s tank?” His answer right off the bat was,
“toluene” much to my surprise. Toluene in this previous research had
not only been found by heating up compressor oils in the lab, but it had
also been found in an air sample collected from a compressor installed
in a very tiny room where the compressor had been suspected of
overheating due to the poor setup and high ambient operating
temperatures. Toluene was not the only volatile contaminant found by
heating up these oils in the lab, but it was one of the most frequently
encountered. Under the right thermal conditions lubricating oil may give
off a volatile vapor from one of its original constituent components or
form new pyrolytic vapor degradation products.
Subsequent to the above discussion a chemist/toxicologist was contacted
who had done work and published several papers in peer reviewed journals
looking at volatile pyrolytic degradation products of different jet
engine lubrication oils. The airline industry about five years ago was
having air contamination incidents with smoke and vapors entering the
cabin air stream via leaking oil seals in conjunction with the thermal
breakdown of the jet engine oils, potentially impairing pilots and
flight crew. After speaking with one of the scientists involved with
this research he too felt toluene production from the thermal or
oxidative breakdown of compressor lube oils was quite possible. This
event would depend on the oil type and brand, the ambient compressor
operating conditions (in particular high temperature), the FO2 of the
gas in the compressor as many of these breakdown reactions are
oxidative, the amount of moisture in the oil, the length of time the oil
had been used in extreme heat conditions, and interestingly what
cylinder and piston ring breakdown products were in the oil at the time
of the incident. Metals such as copper and iron which enter the oil sump
from piston ring and cylinder wear/breakdown act as catalysts to many of
these oxidative and pyrolytic reactions. He suggested that not only
should the breathing gas be analyzed at the time of a contamination
incident, but a sample of the used compressor oil be collected for
analysis of its condition and for later thermal degradation studies in
the lab. In other words just heating up the same brand and type of new
oil from a compressor where contamination is suspected may not always
yield the vapor contaminant(s) in question as the catalysts, moisture,
and acids are missing which become part of the oil mixture with
compressor use over time.
The possible production of compressor lube oil volatile hydrocarbons
which may be toxic to divers is an area where a systematic study of all
the commonly used oils needs to be done in an academic setting. The
various synthetic diester and triester oils, and the newer ?safer
polyalphaolefin (PAO) oils need to be thermally exposed at pressure with
catalyst and oxygen in the case of continuous blending to see at what
temperatures they start to breakdown and what may be the pyrolytic vapor
degradation products. As with the jet oils, the temperatures reached and
type and brand of oil are factors in these degradation products.
Why these studies have not been done to date by the oil lubrication
companies themselves is a good question, but I suspect the answer I
received from one oil company executive is quite representative.
“Breathing air applications require a qualified filtration system to
certify the oil for breathing air.” In other words if you have proper
filtration which is functioning it doesn’t matter what the oil gives
off at high temperature as the “qualified filtration system” will
capture the contaminant. This may be partially true, however it would be
prudent to know in the case of breathing gas production if a particular
brand and type of oil when subjected to high temperature, pressure, FO2,
and wear gives off some toxic volatile vapor with a low margin of human
toxicological safety should a filtration breakthrough occur. Also there
may actually be certain contaminants produced from only certain brands
or types of oil that are poorly removed from the air stream by standard
scuba filtration or are very toxic and even with a “qualified
filtration system” they present too high of a risk to divers to be
used in breathing air production.
The lubrication companies seemed to have passed the buck on this one to
the folks designing, operating, and maintaining the compressor and
filtration systems we use. Their oils under certain thermal conditions
may in fact produce toxic volatiles, but they feel as long as proper
filtration exists there is no need to worry. This places a very large
onus of responsibility on fill station operators to be aware of these
heat related vapor risks, and to ensure a “qualified filtration
system” does exist at all times between the diver and these potential
contaminants. Unfortunately though most fill station operators are not
well educated in these risks, and measures such as proper compressor
installation, ventilation, and maintenance so as to prevent the oil
overheating and volatizing in the first place are not instituted. Under
specific conditions therefore, and likely sporadically when a
“qualified filtration system” suddenly becomes “unqualified”
with a toxic volatile vapor present due to excessive oil temperatures,
serious diver injury or death can occur.
Upon speaking with several of the lube oil companies they do see this
issue as one mainly to do with compressor design and poor maintenance as
well as inadequate and improperly maintained filtration. One oil company
representative commented on the poorly designed small compressor oil
sumps and volumes which lead to inadequate oil cooling and problems with
oils overheating in the compressor system especially with extreme use in
high temperature and humidity geographic regions. Another mentioned the
large variations in frequency of oil change intervals between what they
recommend and what the compressor manufacturers recommend. This
particular company said synthetic oils should be changed out at 200
hours in normal conditions and at 50 to 100 hours in Nitrox blending
situations or high ambient temperature and humidity conditions (those
typically found at Florida stations during the summer). Running high FO2
mixes through the oil substantially decreases the oil’s life
expectancy especially in conjunction with high temperature and humidity.
As the oil starts to degrade irreversibly under these conditions the
viscosity and acidity increase which leads to further compressor stage
overheating and more oil thermal degradation and vapor risk as the oil
loses its ability to dissipate frictional heat. The only way to
determine the condition of an oil at any point in time is thru
laboratory oil analysis which is a whole other science unto itself.
One wonders why all breathing air compressors are not required to have
an oil temperature gauge and high oil temperature shut down switch. This
would at least alert the fill station operator to conditions where
thermal degradation conditions may start to occur. Bauer sells and sets
its “optional” oil temperature alarm at 175 F. Ultrachem the
manufacturer of Chemlube products states, “as temperatures increase
the oil life is drastically decreased, especially above 220 F,” and
with its synthetic oil cuts the oil’s life expectancy down drastically
for each ten degrees above 180 F.
There is very good circumstantial evidence therefore that toluene can
result from the thermal and/or oxidative degradation of a compressor
lube oil which will give rise to an internal compressor source of
toluene contamination. The exact temperature and other conditions
required (moisture, metal catalysts, etc.) for this reaction to occur
however are not known at this time. It is very clear though that
academic thermal laboratory studies are needed on these compressor
lubrication oils both for the diester and triester synthetics, and for
the newer food grade polyalpholefins to determine what the potential
toxic pyrolytic and oxidative degradation vapors may be for both the
SCUBA and SCBA communities.
It would also be beneficial if an independent laboratory could do an
analysis of the commonly used oils for high pressure reciprocating
compressors examining how these oils wear over time with respect to
oxidation resistance, water resistance, etc. Fill station owners would
then not have to rely on potentially biased proprietary information from
the oil manufacturers regarding an oil’s suitability and life
expectancy under typical and extreme (high heat) compressor conditions.
3) Toluene Filtration Breakthrough: How did it happen?
It is interesting to note that many of the experts I spoke with were
not entirely surprised that toluene might appear in the pre-filtration
gas stream as a lubricating oil thermal or pyrolytic vapor degradation
product, but were quite surprised that the toluene vapor was able to get
by the chemical filtration and end up in the diver’s tank. In fact one
scientist who works for the largest carbon manufacturer in the world and
supplies coconut shell based activated carbon to Lawrence Factor and
Bauer for their breathing gas filters summed it up very succinctly. He
said, “The only way toluene ended up in the diver’s tank was that
the activated charcoal in the filtration was not just wet, but very wet
probably well above the 80 percent humidity level.” In other words the
filtration was saturated with moisture and no longer protecting the gas
stream from this contaminant at the particular time the banks were
filled. This was made quite clear by this scientist.
As he explained, activated charcoal will adsorb various vapors some very
efficiently like toluene and some are poorly adsorbed like carbon
dioxide (CO2) and carbon monoxide (CO). In the case of CO we add
Hopcalite to the filter cartridge before the charcoal bed in order to
catalyze the oxidation reaction of CO to the less dangerous CO2. This
vapor adsorption by the charcoal bed depends on the size of the bed, the
charcoal pore size relative to the molecule in question, the vapor
pressure of gas, the polarizability of the molecule, the temperature of
the gas stream, and the shape of the molecule with the aromatic
hydrocarbons having the best adsorption of all. Toluene is an aromatic
hydrocarbon and should normally be highly adsorbed by the activated
charcoal. In this particular case though, the desiccant or sieve
normally responsible for the absorption of water vapor from the gas
stream must have become saturated allowing the charcoal bed’s humidity
to increase sufficiently such that it was no longer effective at
removing the toluene from the gas stream. This phenomenon of a vapor
passing directly through a bed of charcoal where normally the
contaminant should be readily removed is known as “breakthrough”.
So how might this happen you wonder and under what conditions? The
question I kept getting asked by these scientists was at what ambient
temperature was the compressor operating at the time of the incident?
For this data I was pointed to the Florida Automated Weather Network
(FAWN) which has historic climatic data and pulled up some interesting
facts.
For the Gainesville area in northern Florida one can access on FAWN the
number of hours a month that the temperature was above a particular
threshold. For reasons that will become clearer below, I chose 65 F (18
C) as the threshold temperature which gave the following results:
Month……Percent Time in Month > 65 F
Jan…………......…….10
Feb…………......……..9
Mar………......……..31
April………......…….38
May……….....……..70
June…….....……….91
July………….....……95
Aug…………....……97
Sept ………....……66
Oct…………....…….57
Nov…………...……29
Dec (2003)...…… 5
If one looks at the daily temperature for the last Sunday in May 2004
(approximate date tank was filled) it ranged from 61 F to 96 F. At this
time of year the temperature did not dip below 65 F until after 0100
hours and was above 65 F again by 0630 hours. By 0800 hours it was 80 F
(27 C) and by 1400 hours the temperature hit a high of 96 F (36 C).
These daytime temperatures would be classified as very high temperature
ambient conditions, and the oil manufacturers would call these
“extreme” conditions particularly if the compressor is set up in a
small poorly ventilated room where ambient temps may be 10 to 20 F
higher than the outdoor temperature due to the compressor’s own heat
production.
In order to understand what likely happened to allow the toluene to
breakthrough one must delve into (suggest coffee break now) how a
cartridge’s processing capacity is determined by the manufacturers.
When Bauer or Lawrence Factor (LF) report their respective filter
cartridge processing capacities this is done at what’s called
“standard inlet conditions.” Unfortunately these standard inlet
conditions are not so standard between the filter manufacturers which
has led to some filter brands reaching their maximal gas processing
capacities much earlier than expected in high temperature ambient
conditions. Once the maximal capacity is surpassed the desiccant can no
longer keep the charcoal bed dry and vapor contaminant breakthrough will
begin if the filter cartridge is not replaced. This is a very dangerous
situation as what was previously a “qualified filtration system” has
become “unqualified”, in other words no barrier exists to protect
the diver from the vapor contaminants which may be present in the gas
stream.
The filtration capacities are calculated assuming the gas entering the
desiccant prior to the Hopcalite and activated charcoal is at a certain
temperature and pressure, and is 100 percent saturated with water at
that temperature. The relationship between temperature and the amount of
water a kilogram of air can hold at 1 atm can be seen in the first graph
below. The important point to notice is the exponential relationship
between increasing temperature of the gas stream and the maximal amount
of water vapor it will carry. One can see that the higher the
temperature particularly above 65 F (18 C) the more moisture will be
carried into the desiccant and as a result it will saturate much faster
with increasing temperature. Molecular sieve 13, a commonly used
desiccant to achieve very dry breathing gas, can hold about 20 percent
of its weight in moisture, but as the gas stream rises above a certain
temperature (> 120 F) the sieve will actually start to release some
of its absorbed water back into the gas stream. Elevated temperature
therefore increases the amount of water vapor carried in the gas stream
to the desiccant, and if the inlet temperature is high enough this will
also decrease the amount of moisture the desiccant can retain.
When it comes to calculating and rating the maximal cartridge processing
capacity, by using a lower standard inlet temperature (less moisture
entering the desiccant) as Bauer does, you actually get to advertise a
higher filter capacity to the consumer. This creative accounting
presents a very significant diver safety issue as with the Bauer
cartridges although they have a higher advertised capacity at this lower
inlet temperature, when they are used in high ambient temperature
operating conditions above the standard inlet temperature these maximum
filter processing capacities must be reduced by very large amounts. Very
few Bauer filter sales personnel or fill station operators are aware of
these vital temperature corrections to filtration capacity for elevated
ambient temperatures, and therefore breakthrough of vapor contaminants
becomes much more likely as the filter becomes saturated with moisture
earlier than expected. Let’s have a closer look at how Bauer and LF
determine their filter capacities.
Bauer calculates and rates its cartridge capacities at their “standard
inlet temperature” of 68 F (20 C). Inlet temperature is the
temperature of the air stream entering the chemical filtration or
desiccant after the final oil/water separator. The difference between
ambient and inlet temperature varies depending on compressor
installation, ventilation, intercooler design, etc., but is somewhere in
the 10 to 20 F range, so say 15 F.
Inlet temp = Ambient temp + 15F.
What this means is that when Bauer says the filter cartridge they just
sold you is good for 40,000 cu. ft of gas processing this is only if an
inlet temp of 68 F or an ambient temp of 53 F (12 C) is maintained in
the compressor room. When was the last time you were at a fill station
where the compressor saw a continuous ambient temp of 53 F while
pumping?!! Certainly I have never seen one in the tropics, however I
know several up here that never see an ambient temp above 68 F (20 C) as
the compressor rooms are air conditioned. Lawrence Factor is a little
more realistic with typical compressor room ambient temperatures as they
rate their cartridge processing capacities at a standard inlet temp of
80 F (27 C) or an ambient temperature of 65 F (18 C) hence the reason I
chose the Gainesville temperature threshold of 65 F.
One can see that any time the compressor’s inlet temperature is above
the temperature where the cartridge capacity was determined a
temperature correction must be made to reduce the filter’s capacity
rating as the higher inlet temperature means more water vapor will enter
the desiccant and it will saturate sooner. This translates into
increased frequency of cartridge changes needed. Let’s have a look at
just how often filter change intervals would have to decrease as the
inlet temperature rises in a typical high heat geographical area.
From the northern Florida temperature data above and assuming most fill
stations in this region are probably using the clear plastic LF filters
with maximum processing capacities set at 80 F inlet, one will need to
make a capacity correction downwards any time the ambient temperature is
above 65 F. One can see therefore that during the winter months of
January and February a correction would only be needed 10 percent of the
time, but during June through August a filter processing correction
would be needed over 90 percent of the time if the compressor was used
outside of the < 65 F time frame. With Bauer filters these
corrections would be needed 100 percent of the time during the summer as
an ambient temp of 53 F is never seen!
During the summer there may only be a four to five hour window in the
early morning were a temperature of < 65 F actually exists. If one is
using a commercial fill station which pumps high volumes of breathing
gas they likely will not be able to meet customer demand especially on
weekends pumping only during these few nighttime hours with lower
ambient temps, and therefore much of the compressor usage time outside
this cooler temperature window will necessitate corrections to the
filtration capacity.
Using the Bauer filter temperature correction factors the extent of this
problem of how easy it is to surpass cartridge processing capacity when
used in high temperature ambient conditions becomes very evident. For a
given filter capacity rating at standard inlet temp of 68 F (53 F
ambient) here are the correction factors to multiply a filter’s
capacity ratings by depending on the actual inlet temps.
(68 F - 1)
(86 F - .57)
(104 F - .34)
(122 F - .20)
At the end of May in northern Florida at 0700 hours with an ambient
temperature of 70 F the correction would be .57 and by 1400 hours the
capacity correction at 95 F ambient (inlet 110 F) is a whopping .25! If
the compressor was run for two hours at 95 F this would have to be
recorded as 8 hours of use in the log book as four times the moisture
would be taken up by the sieve at this temp compared to 53 F. A typical
33 inch multiplex filter rated for 40,000 cu. ft of processing is only
good for 10,000 cu. ft at an ambient temp of 95 F or one quarter of what
its capacity is advertised for by Bauer. For the months of July through
August a fill station would have to be switching out its filtration
approximately two to four times as frequently than during the winter
months. One can see then if an owner did not correct the filtration
capacities for these high summer temperatures the desiccant and charcoal
would become saturated well before the filters were changed based only
on “standard inlet temperatures.” Any vapor contaminant if present
would therefore start to breakthrough and enter the storage banks and
diver’s fills. If a volatile vapor was present due to the thermal
breakdown of the compressor’s oil under the same high ambient
temperature conditions, the gas would likely start to have an oily or
solvent smell to it at this point in time.
With the LF filters the temperature correction factors are slightly
lower as the standard inlet temp they use to rate their cartridges is
higher to begin with. At the same inlet temp of 110 F an LF cartridge
would require a correction to its capacity of about .4 compared to a
Bauer factor of .25. (see 2nd graph)
As the only barrier that exists between a diver’s tank and toluene or
any other vapor contaminant present is the existence of functioning
desiccant which continues to keep the activated charcoal and Hopcalite
dry, it becomes imperative in any high heat geographic area, but
particularly at those where commercial fill stations are pumping large
volumes of gas on a daily basis to know exactly from hour to hour the
state of their desiccant’s saturation status. Otherwise, if the
saturation status is not known in real time, once the charcoal becomes
wet any vapor phase contaminant in the gas stream will begin to
breakthrough the filtration contaminating the diver’s fill and
creating a high risk situation for diver injury. With high volume
commercial fill stations this could happen very quickly before a problem
was recognized.
One can see that as compressed breathing gas production moves from the
small ‘artisanal’ or homebrewed means of production to one of large
scale industrial production real time digital moisture and CO monitors
should become mandatory at these large fill stations in order to protect
the diver from sudden loss of a “qualified filtration system” and
subsequent breakthrough of potential lube oil thermal degradation
products into the fills. Many commercial fill stations may have made the
leap to industrial quantities of breathing gas production without the
necessary transition to proper industrial compressor installations where
heat reduction becomes paramount, and monitoring of the gas stream
quality occurs in real time using quantitative high pressure
instruments. While the volume of gas produced may be at industrial
levels at these high volume commercial fill stations often the
monitoring of this gas quality remains at the “mom and pop” level.
After, a question came up from Oxyhacker:
I guess the big question is, that if this was a simple
case of filter exhaustion, then wouldn't there have been a breakdown
across the board in air quality, with oil and water present in such
quantities that even a cut-rate analysis - or for that matter, a
handkerchef test - could not have missed it? One would also assume that if
this was the case it would have been easily noticable afterwords when they
returned to the shop - normally, one of the first things one does in a
case of suspected contamination is check the filter condition
The answer was:
Very good question.
In the CGA Gd E analysis the oil and particulate analysis and the total
volatile hydrocarbon analysis often lead to confusion as to what each
tests for.
Oil and Particulate Analysis
The oil and particulate analysis looks for the condensable hydrocarbons
or oil mist by trapping these on a filter paper, and then weighing this
filter before and after the test to determine the final concetration of
oil mist. Usually if the compressor is running too hot the oil is
vaporized temporarily but condenses downstream in the tubing, banks, and
your tank if in high enough concentration and with sufficient flow to keep
it aerosolized and moving.
This same technique is what the military uses to create fog oil so as to
obscure soldiers' movements. A mineral oil is poured into a heated
manifold which vaporizes the oil and upon contact with the cooler
atmosphere a condensation aerosol is form. If you were filling right off
the compressor which was running too hot you would likely get a similar
fog oil aerosol in your tank, but overtime this would settle and stick to
your tank walls. Once this hot oil vapor though hits the cold high
pressure tubing, banks, fill whips, and finally possibly your tank it has
condensed back to the same oil more or less as is in the compressor.
It would be possible to catch this mist on a hankerchief if in high enough
concentrations and still present in an aerosol form but usually with time
this mist will settle out and stick to the tubing and bank walls. This is
why one needs a very high flow and of sufficient volume during sampling to
mobilize these condensed oils. For this reason it is not possible to do a
proper oil and particulate analysis off a scuba tank for forensic purposes
as the scuba tank oil once on the tank walls cannot be remobilized for
analysis. You need to go back to the original compressor system and flow
at a minimum of 8 cfm for five or ten minutes to get the oils mobilized
from the storage banks and tubing onto the filter paper.
This oil mist is also what one tries to minimize in the production of
oxygen compatible air for PPM.
Total Volatile Hydrocarbons (TVHC)
These are not condensable oils and remain a vapor in the true sense of
the word a they exist in the gas phase which is different than the liquid
particulate or aerosol above. In this pyrolytic oil degradation incident
above all the suspected lube oil volatile degradation products fall into
this TVHC category. As they are volatiles they will not be trapped on a
hankerchief or filter as they are gaseous. Toluene and all the BTEX
compounds would be found in the TVHC analysis not oil and particulate
analysis. These volatiles are identified with a gas chromatograph/mass
spec whereas the oil mist analysis above is simply a gravimetric test, pre
and post test filter weigh.
From a health standpoint high concentrations of oil mist which has a low
vapor pressure will not enter the blood stream but will end up being
deposited in your lungs and may cause a lipoid pneumonia well after your
dive. You will come home at the end of the day but will likely develop a
nasty cough in the subsequent days.
An elevated TVHC either from toluene or some other volatile organic
hydrocarbon from the pyrolytic degradation of the lube oil is a much more
serious issue. These vapors enter the blood stream rapidly and can cause
narcosis and death depending on concentration, depth of the dive,
exertion, and duration of exposure. They enter our CNS tissues rapidly and
impair cognition. You may not come home from your dive with these onboard.
A hankerchief will not find these volatile HCs but your nose will. Very
low cost and low tech way to protect yourself
As for the second part of your question it is a little more difficult to
answer but I will give it a shot. Maybe Barney or Joe can chime in but I
do recall one of them saying they returned to shop to speak with the
person filling the tanks. Remember though there was a one month interval I
think between the fill in question and the dive in question so the
situation at the fill station at the time of the incident was likely not
the same as when the fill was done a month prior, however they did detect
a similar smell on some of the fill whips at this time.
Filtration breakthrough is a complicated business depending on numerous
factors and I suspect is much like tornado prediction. We know the
conditions a tornado is likely to form under but predicting where the
first tornado will touch down is far more difficult.
Upon speaking with the the carbon scientist who also happened to be a
diver as well and was most interested in this case, it became apparent
that breakthrough is not an all or nothing event. Assume the desiccant is
near saturation and the compressor is running at 1400 hours when the
ambient temp is 95 F or likely well over a 100 F in the compressor room.
The inlet temp will be even higher probably pushing the 120F limit for the
molecular sieve. All of a sudden the sieve gives off a burst of water
vapor as its ability to retain water at this temp is compromised. The
charcoal bed's humidity rises suddenly to a level where it can no longer
adsorb the vapor contaminant effeciently and vapor breakthrough spikes
start for the duration of the compressor run. If the compressor is run
later at 0400 hours when things are cooler there may not be sufficient
temperature to get pyrolysis of the oil and the sieve at the lower
temperature is protecting the carbon again.
Alternatively one can have relatively dry charcoal but if the contaminant
vapor is high enough or fluctuating breakthrough can occur. When the
contaminant concentration is fluctuating rather than steady state the
breakthrough spikes occur much earlier and at higher levels. This can be
seen here in some work done at DCIEM. Figure 3 page 32 shows this effect. http://cradpdf.drdc-rddc.gc.ca/PDFS/zba15/p151935.pdf
A rather long winded answer I know, but no the hankerchief will not find
these volatile hydrocarbons however the nose may. It is possible to get
breakthrough with dry carbon and fluctuating contaminant levels, or from
wet carbon that is no longer effective which is the more common scenario.
The latter situation would occur in high temp regions where there was no
attempt by a fill station operator to monitor desiccant saturation status.
The simple answer too all these problems is keep compressor heat
(now a four letter word I hope) down at all costs and why Bauer is
"rabid" about compressor installation and ventilation.
4) Determining Desiccant Saturation Status
If the only thing keeping a diver from being poisoned is a
“qualified filtration system” between you and potential gas stream
contaminants then the first question an educated diver should ask a fill
station owner is, “How do you determine when your filtration is
saturated with moisture?” If the owner gives you a blank stare then
the next question you should ask is, “When did you last change your
filtration?”, especially if in Florida between May and September! If
he says yesterday then you are probably safe, but if he says eight weeks
ago you probably want to be careful if it is a high volume station
during a heat wave at the end of a busy weekend.
It should be very apparent now why all fill station operators should
have some method of determining the moisture saturation status of their
filtration if they are to prevent these contaminant vapor breakthrough
incidents from occurring. Sadly most do not make these filtration
processing capacity temperature corrections or do not have a real time
device to determine saturation status. This is often the case because
these operators have not been educated either by their compressor or
filtration manufacturer on the importance of these issues, and there are
very few courses or certifications where one can go to learn the ABCs of
safe gas production covering everything from compressor installation to
breathing gas analysis. To add to the problem a moisture analysis is not
even required as part of the CGA Grade E standard air analysis (one is
required under Canadian CSA Z180.1 analysis) so it is possible a fill
station could have absolutely no idea as to the moisture status of its
filtration at any point in time other than using the hour meter and
filter capacity rating at standard inlet conditions. Think of these
issues the next time you visit Mexico’s Yucatan Peninsula or Palau and
there is no air quality assurance program period, no temperature
corrections being done, or no real time monitor to determine moisture
saturation status of the filtration, yet they are filling 500 AL80’s a
week in a tiny compressor room with inadequate ventilation. These types
of geographic locations with year round high heat conditions, lots of
diver traffic, and no monitoring of filtration status other than the
hour meter represent high risk fill stations for gas contamination
incidents.
So what methods are available to detect moisture levels in filtration?
Here is a brief description of the current methods from the low tech,
low cost to the high tech, high cost. The home brewer or 100 hour a year
fill station can stick to the low tech gear, but as one gets into
pumping 40,000 cu. ft of gas a week especially in high temperature
climates, the high tech devices should be required to protect the
diver’s gas supply from filtration moisture saturation and contaminant
breakthroughs.
Current methods available for saturation status determination
1) Temperature logging
One logs temperatures by the hours of compressor use and then applies
the correction factor to increase the number of hours for the higher
saturation rate. This method is tedious but would be suitable for home
and smaller fill stations. Very low tech and free of charge.
Example (Bauer filters and ambient temp)
Logbook for May 25
95 F 2 hours 2/.25 = 8 hours
70 F 6 hours 6/.57 = 11 hours
So 8 hours of actual use is now corrected to 19 hours towards the rated
maximal processing capacity at standard inlet conditions.
2) Filter with visible humidity strip
Lawrence Factor cartridges which are clear plastic have a humidity strip
on the inside which changes from blue to pink when the relative humidity
reaches 40% at pressure. This corresponds to a dewpoint of about – 40
F at which point the filtration should be changed out in warmer
climates.
In colder climates where one is concerned with freeflows during cold
water diving the dewpoint needs to be much lower than -40 F usually at
least -65 F (-53 C), and filtration would need to be changed much
earlier so as to maintain sufficiently dry breathing gas. See method 4
or 5 below for what to do in this coldwater case.
The only problem with this humidity strip method is one has to take the
actual cartridge out of the filter appliance in order to see the
humidity strip, but at least there is some real time potential. The
danger though is if one doesn’t also correct for high ambient
temperatures while using the humidity strip, it will turn pink well
before the fill station owner figures it is time to check the cartridge
leading to loss of “qualified filtration” and gas stream contaminant
protection. This situation of having the humidity strip inside the
filter stack is akin to having your car’s gas gauge inside the trunk
of the vehicle. At some point the operator will be too lazy or forget to
check the gauge and the car will run out of gas. A filter humidity strip
will though provide an additional check to your temperature adjustments
if logging compressor hours.
3) External visual humidity detector
Combining an external visual humidity detector either after the first
desiccant only filter or after the last triple media filter (desiccant/Hopcalite/
activated charcoal) with the LF humidity strip above is probably the
cheapest and most reliable low tech, low cost way to go. Definitely with
the filter cartridges such as the aluminum Bauer ones which don’t have
a humidity strip this device should be the bare minimum standard and
should be used in conjunction with temperature corrections as a
secondary real time back up.
Every commercial fill station should have one of these detectors for
humidity as a bare minimum to get an idea as to what the filtration
saturation is doing in real time. Temperature corrections can be off
during heat waves and often inlet temperatures can be higher than
calculated. This simple low tech, low cost device provides decent real
time moisture check without removing the cartridge. Essentially this
moves the car’s gas gauge out of the trunk back onto the dash where it
should be. For homebrewers who are packing their own filter stacks with
media this little device would also allow one to judge when the
desiccant is saturated again though for warm water diving.
The device only costs $80 US and is available from GMC Scuba (part
#44070). The replacement sensor elements (#44071) with the humidity ring
and CO sensor dot in the center are about $8 and should be replaced
yearly. The humidity sensor ring changes color at 40 % RH or about -40 F
(-40 C) at 3000 psi, similar to the LF filter humidity strip above. www.gmcscuba.com
4) Colormetric Tubes
Often known as ‘Draeger’ tubes these tubes are available to measure
moisture down to extremely low levels. There are several kits on the
market which can measure CO, CO2, moisture, and oil vapor
simultaneously, but these multigas field analysis kits are not cheap,
usually in the range of $800 to $2500 US. Several of the breathing gas
laboratories if using their services should be able to provide a
moisture only colormetric device for considerably less. One would then
do serial dewpoint measurements and change out the filtration when the
dewpoint approached what was determined acceptable for the dive
conditions. As mentioned above at a cold water dive fill station one
would want to think about switching out the filtration when the dewpoint
had reached -65 F (-53 C) so as to minimize freeflows. In water near the
freezing point a dewpoint usually in the -90 F (-70 C) range or drier is
recommended. In these cold water conditions the visual humidity detector
above would not be adequate to ensure dry air.
5) Inline real time dewpoint meter
The highest level of protection involves considerably more money and
maintenance, but these high pressure inline dewpoint (and CO) meters
available from Cosa Instruments or Nyad Inc. will give you real time
digital dewpoint readings. The units though do require regular
calibration to maintain accuracy. Any commercial scuba station
especially those in the industrial category pumping high volumes of gas
in high temperature geographic regions should have one of these real
time dewpoint meters on their breathing gas systems in order to monitor
moisture status and ensure there is a “qualified filtration system”
present at all times. With these devices one no longer must rely on
temperature corrections and when filling banks around the clock one can
just check the meter and see exactly where either the pressure or
atmospheric dewpoint is sitting. www.nyad.com/Series_600.html
5) Prevention of Gas Contaminant Episodes and
Assessment of a Fill Station’s Potential Contaminant Risk
What should be fairly clear now I hope is why HEAT is a four letter
word in the compressed breathing gas production business. If an ounce of
prevention is worth a pound of cure then that ounce is simply keeping
the oil and filtration inlet temperatures as low as possible during
compressor operation.
In summary then, in order for this toluene incident to have occurred two
conditions were met simultaneously which allowed the diver’s tank to
become contaminated. Remember contamination will not necessarily occur
if the oil degrades and there is a good filtration barrier to capture
these new degradation vapors. Likewise if the filtration saturates just
through normal use at low ambient temperatures there may be no danger if
the gas stream remains contaminant free.
1) OIL BREAKDOWN: The lubrication oil degraded likely due to oxidative
and/or thermal breakdown producing the narcotic gaseous vapor toluene.
It should be noted these are new gas phase vapors formed by the
pyrolysis of the lube oil and are not thought to be part of the original
oil or its light chain odor vapors. The new vapor formation is dependent
on the original oil’s composition which includes base stock and
additives. This original oil plus the wear and tear additions of
acidity, moisture, and metallic cylinder breakdown products allows the
production of new thermal degradation products such as toluene when this
mixture is exposed to high heat, pressure, and hyperoxic environments in
the compressor system. Unlike the original oil which may vaporize if
overheated and condense into an oil mist downstream in the compressor
system, these new degradation vapors remain in the gas phase and are not
found in the CGA Gd. E oil and particulate analysis. They would likely
show up in the total volatile hydrocarbon analysis.
2) FILTRATION BREAKTHROUGH: In order for the toluene produced to
breakthrough the activated charcoal bed the desiccant must become
saturated with moisture usually from excessive inlet temperatures. The
humidity level in the charcoal bed reaches a critical moisture level and
breakthrough spikes begin allowing the toluene to enter the storage
banks or individual tanks if filling directly off the compressor. This
critical moisture breakthrough level is different for each gaseous
contaminant and also depends on numerous other factors such as whether
the vapor concentration in the gas stream is steady or fluctuating.
I have tried to think of a good analogy that divers might remember so as
to reinforce the dangers of operating a compressor with a compromised
filtration barrier, and also be one which might approximate the health
risk that exists when contamination does occur due to the loss of
qualified filtration.
One might want to consider what happens when your dentist’s sterilizer
goes down for a day or two without the dentist knowing. Normally the
only barrier that exists between you in the dentist’s chair and the
previous patients’ blood borne diseases is a properly functioning
instrument sterilizer. When that sterilizer malfunctions unless the
previous patients were all nuns then chances are with a day's worth of
dental patients that several of these patients will have a transmissible
blood borne disease. If the instruments remain contaminated due to loss
of sterilization there is a good chance you will become infected and
sick at a later date. Office sterilizers are usually checked monthly in
an ideal world for proper functioning but do malfunction sporadically
for various reasons. When sterilization does not occur adequately one
will get sporadic disease transmission within medical and dental patient
populations. These diseases are often serious and potentially lethal.
Likewise with a breathing gas compressor system the only barrier between
you the diver and any vapor contaminant such as CO, CO2, or narcotic
vapors such as toluene from the thermal breakdown of an oil is a proper
functioning filtration system. Once this filtration goes down and one of
these contaminants is present in the gas stream, there is no better way
of delivering this contaminant rapidly to your tissues than by
inhalation at high partial pressures. If the contaminant partial
pressure is high enough and the exposure of sufficient duration you may
die early in your dive on descent, or sometime thereafter as exposure
duration increases. If a thermal degradation vapor was the cause of
death chances are the death certificate or coroner’s report will not
reflect the true chain of events which lead to your demise. Drowning,
heart attack, and physiological causes come to mind.
If you don’t like the idea of going to your dentist without a
functioning sterilizer between her last patient and your blood stream,
then you should be far more concerned at any fill station where the
proper functioning of the only barrier between you and potential gas
stream contaminants is undeterminable, or left in the hands of an
operator who is unaware of the potential health risks to the diver
should this barrier become compromised.
A functioning filtration system therefore needs to be verified in real
time each time the compressor is running especially in geographical
locales with high ambient heat where desiccant saturation is much more
rapid. If not verifiable, just remind yourself of that dentist with the
broken sterilizer who had a few IV drug users as patients the day before
you arrive! A compressor’s filtration system is in effect our gas
“sterilizer” so as to prevent gas borne disease.
Assessment of Compressor Station Potential Contaminant Risk
Let’s assume we arrive on holidays to do some deep technical diving in
Palau (average yearly temp is 82 F with 85 percent humidity). At the
local fill station we wonder how can I assess the quality of the air
that is going to be used for partial pressure mixing or continuous
blending? What can a diver look for at the fill station to determine the
potential gas contamination risk? While walking around the compressor
system setup it should be clear now that minimizing heat in the system
is the name of the game, and the identification of poor installations
where overheating is likely should raise lots of red flags.
1) Geography and climate.
Any area with sustained high heat and humidity will be higher risk for
contamination episodes so one needs to be much more careful in these
areas. Excessive heat leads to oil pyrolysis and faster filtration
moisture saturation. The safety margins are much smaller for poor
compressor installations and/or poor maintenance in high heat and
humidity locales. Remember if ambient is 90 F outside the compressor
room then after an hour of operation in a tiny room with no cross
ventilation the ambient temperatures can easily be over 100 F, and your
inlet temperature will be 15 F higher than that. If the intake for the
compressor is not located outside this room then the compressor will
entrain hotter and hotter air as that room heats up. Filtration
saturates very quickly in these conditions often five times faster than
at standard inlet conditions and ultimately the desiccant starts to
release moisture previously contained.
2) Inspect the compressor set up
a) the remote intake if present should be of large diameter ideally 3
inches or greater with minimal elbows and the shortest possible length.
Long narrow intakes lead to compressor overheating. It is the radius of
the intake that mainly determines resistance to flow. When you see long
narrow intakes often with a clogged debris filter on the end think of
the compressor having to breathe through a long narrow straw.
b) check what is around the intake: fuel refilling stations and vehicles
nearby should be red flags if a remote intake
c) most important is the compressor’s room size and ventilation. If
the ambient temp is 90 F and you walk into the room with the compressor
running and it feels much warmer then you really want to determine how
the owner is assessing the moisture saturation status. There shouldn’t
be more than one compressor in the room running at the same time unless
proper ventilation exists. Remember those LF filter capacities are
determined at an ambient temperature of 65 F and the Bauer ones at 53 F.
Bauer suggests allowing 1100 cu. feet minimum for a typical SCUBA
compressor room with lots of cross ventilation and if the room is
smaller there should be a proper high capacity exhaust fan or ideally
the room cooled with air conditioning (see link) Many of the large SCBA
stations are now air conditioned so as to maintain inlet temps at 80 F
(ambient 65 F). http://thedecostop.com/forums/showp...16&postcount=44
d) If the compressor is against a wall with no intake vent in that wall
at least 18 inches should exist between the wall and the compressor fan,
36 inches is better.
e) If you are in a high heat region and at a busy fill station you want
to see lots of filtration towers probably a minimum of three 33 inch
towers after the final separator. If you only see one or two 33 inch
filtration towers you know the those filters are going to require close
monitoring for moisture saturation status and frequent changes. Think
about that dentist with no sterilizer!
3) Ask for the most recent air certificate.
Not terribly useful if being done quarterly and the last one was done
three months prior to your arrival. In fact it is just about useless for
determining anything three months after the fact. If there is no
moisture analysis it even is less useful. An air analysis is really only
representative of the gas quality on the day it was done and much can
change in that three month interval such as a long heat wave and/or the
oil reaching the end of its useful life.
4) How is filtration saturation status being determined?
If there is no certificate as is often the case at these tropical dive
fill stations then the most crucial piece of data you can determine is
when the filtration was last changed and what the owner is doing to
determine when the next change is required. As mentioned previously, if
there are no temperature corrections being done, no humidity strips on
the cartridge, or no inline eyeball humidity detector then one should be
very careful if the filtration has not been changed for sometime,
especially if planning to head to 10 atm. If deep technical diving and
there with a group you might even offer to pay for a filter change if
you didn’t like what you saw at the fill station. At least if you see
new filters go into the stacks then even if the oil is too hot and
starts to degrade there will be a barrier of “qualified filtration”
between you and any gas stream contaminant for your week of diving.
5) Ask when the fill station manager fills his storage banks.
You don’t want to hear the compressor running in the noon day sun but
rather after midnight when the ambient temps are coolest. Those
correction factors are lowest at this time and the cooler temperatures
will prolong filtration life and minimize the potential for oil thermal
degradation.
6) High air and oil temperature alarms
In an ideal world all compressors should have these with a shutdown
switch. Our cars have temperature gauges so one wonders why on a
breathing air compressor this is not standard gear as well. In Canada
the most recent breathing air standard now requires high air temperature
alarms on all compressor systems. There is usually a sensor in the final
stage head which will shut down the compressor if running too hot.
Tank Field Checks
1) Last but not least even after this walk around assessment of the fill
station use can your high tech, low cost nose to field test each and
every tank especially if you detect a fill station that looks high risk.
Your nose should be able to detect low levels of volatile hydrocarbons
in the gas and at least warn you about a problem before diving in. If in
doubt ask someone else to smell the tank and if still in doubt don’t
dive period. A heavily contaminated tank on descent may kill you in a
few minutes at 10 atm especially if working against a current. You can
be assured that any fatality investigation in a place like Palau will
not involve a proper forensic gas analysis and the death certificate
will likely report a heart attack or drowning. It is therefore up to the
educated diver to identify and avoid high risk fill stations ahead of
time so as to prevent these incidents.
2) Carry a portable low reading quantitative (0 to 70 ppm) carbon
monoxide detector to fill stations you are unfamiliar with. They can be
had for $80 and are cheap insurance against this odorless, irritantless,
and colorless potentially lethal contaminant. If there is > 2 ppm CO
I’d be very suspect about other contaminants being present like CO2 or
some volatile narcotic vapor. It is also not uncommon in some of these
tropical locations off the beaten path to find filtration that has no
Hopcalite in the cartridge to convert any CO in the gas stream to carbon
dioxide.
6) Future Research Needed and Forensic Gas Analysis
Research into diver’s air/gas quality over the years has been
woefully inadequate. One is hard pressed to find any studies
systematically looking at gas contamination incidents likely because
there seems to be a bias in belief that these incidents occur so
infrequently as to be insignificant. The problem though is unless one
does a forensic gas analysis in all dive fatalities it will remain
unknown whether a gas contamination problem was the true initial injury
and first event in the chain which led to, for example, the seizure or
respiratory distress on descent, the disorientation in a cave and
subsequent drowning, or the chest pain and pulmonary barotrauma from a
rapid ascent. If we don’t consider gas quality problems as a possible
initial injury event from which many of the other injury categories may
follow, then the status quo of reporting these likely sporadic gas
contamination fatalities as heart attacks or drownings of unknown cause
will only continue.
In fact, if one examines the DAN fatality data for the years 1995 to
2000 twenty-eight percent or 145 fatalities (approx. 30 fatalities a
year) are recorded as a near-drowning or drowning with the initial
injury “unknown.” That is a very large number of fatalities year
after year with no antecedent cause identified, and no research into
what might be the injury mechanisms behind this category of unknown
drownings. I think it is quite easy to speculate given the degree of
cognitive impairment Barney experienced in this incident that had the
initial toluene concentration been higher, or at a higher partial
pressure at depth the ending may not have been as benign as it turned
out. One suspects in this incident had the outcome been a fatality with
only the first gas analysis done that there would have been yet another
drowning of “unknown” cause added to the DAN statistics.
Better data needs to be kept on the events which occur prior to a
drowning or near drowning incident. Antecedent details such as what was
happening on descent with regard to the diver’s behavior and
respiration need to be recorded as it is during the descent when many of
these contamination episodes will present. Was the diver panicky and
anxious indicating a possible CO2 incident, or was she dream-like and
drowsy before spitting the regulator out for no reason indicating a
possible narcotic vapor in the gas supply?
It is probable these gas contamination fatalities are sporadic and occur
only when a sufficient number of fill station risk factors as described
above coincide together in conjunction with a sensitive diver whose
individual predisposition depends on many factors such as age, fitness,
smoker, medications, etc. As mentioned earlier, the technical diver will
always remain a very sensitive “canary” for these contamination
problems due to the high partial pressure contaminant exposures at
depth. The time may have arrived for divers to encourage DAN to begin
looking at this issue of SCUBA compressed gas quality a little more
seriously by committing some resources for research studies into this
topic. Improved breathing gas quality may in fact remain one of the last
frontiers of dive safety overlooked by the industry, and with
improvements in this area a significant drop in the numbers of
fatalities may occur worldwide.
If you ever find yourself involved with a fatality investigation insist
as the diver’s buddy or family member that a forensic gas analysis be
done by an accredited lab which participates in the Compressed Air
Proficiency Testing (CAPT) program. The CAPT program is a quarterly
testing program done by a university third party laboratory to ensure
the lab you use is producing reliable results for the gaseous components
of the analysis (moisture, oil and particulates are not part of the
program). The US Navy requires all its external contract and specialty
labs to use the CAPT program and at this point in time the Navy uses
Analytical Chemists, Inc. (ACI) in San Diego, and TRI Air Testing Inc.
in Texas for the bulk of their outside testing.
Remember a gas sample should be taken as soon as possible after the
incident as some of these degradation vapors may be unstable over time
which will lead to a drop in their concentration the longer the gas sits
in the tank. Likewise the sample once taken should be forwarded to the
lab without delay. A moisture analysis should always be requested as an
elevated dewpoint may indicate the filtration was sufficiently saturated
to allow the contaminant to breakthrough into the gas stream and storage
banks. A sampling kit from ACI as shown in the thread photos could be
sent by overnight express to any global location in order to assist the
local authorities if a high quality breathing gas lab was not available.
The sample flask is low pressure so it can travel by air without any
restrictions.
Although possibly difficult to obtain under these circumstances, in the
event of a fatality where gas contamination is suspected one should try
and take a small (50 cc) compressor oil sample from the system where the
gas originated from. This oil could be heated up at a later date and
again be used for forensic analysis into the origin of a toxic
degradation vapor.
One of the high priority areas of research which needs to be done in an
academic setting is a study looking at the pyrolytic degradation vapors
of the commonly used compressor lube oils such as Chemlube 751, 800,
Summit DSL-125, and the newer PAO oils such as EZ-1000 and CF-2000. Not
only would the unused oils need to be exposed to heat, pressure, and O2
similar to those found in an overheated compressor system, but also oils
that have come from extensive use in the field under real conditions of
high heat with all their ‘wear and tear’ components need to be
heated up in the lab as well. These used oils may produce a different
set of new degradation vapors not found with the unused oils. As
mentioned previously there is already a group of physicians,
toxicologists, and chemists who have been involved in researching
similar problems of air contamination in the aviation industry from
degradation of jet engine lube oils, and whose expertise could be used
to investigate our compressor lube oil concerns and SCUBA breathing gas
quality. The SCBA community is also very interested in these problems as
well, but more from a chronic exposure standpoint to these potential
breathing air contaminants.
As for compressor filtration it is time to put an end to the creative
accounting with the advertised maximum processing capacities and have
all the filter manufacturers rate their filters at the same “standard
inlet conditions” using a realistic inlet temperature. My suggestion
as the bulk of diving does occur in warmer parts of the globe would be
to standardize at an inlet temperature of at least 85 F (29 C) which
gives an ambient of 70 F (21 C) for the compressor room. For Bauer to
standardize their filter capacities at an inlet temperature of 65 F is
at best misleading, and very much a diver safety issue especially when
the company and filter resellers do not seem to educate the fill station
managers purchasing the filters about the need to make the huge capacity
reductions in high heat climates.
All commercial fill stations must have a method to determine in real
time the moisture saturation status of their filtration especially in
the high heat geographic areas where filtration will saturate much more
quickly. An eyeball humidity detector with manual temperature
corrections or filter humidity strips should be a basic requirement on
all compressor systems. The installation of oil and air high temperature
alarms with shutdown switches should be considered mandatory with large
commercial fill stations in tropical regions as should the installation
of real time digital moisture and CO meters when the quantity of gas
pumped is in the industrial range. Greater education and possibly
standards regarding the proper installation of breathing air compressor
systems in order to minimize overheating should be considered as basic
preventative measures against gas contamination incidents.
Lastly some serious consideration should be given to the establishment
of a commercial fill station operator’s certification course which
would cover the ABCs of proper compressor plumbing, installation, and
maintenance through to the science of breathing gas analysis. It should
be emphasized in such a course that a proper functioning filtration
system is the diver’s gas "sterilizer", and this filtration
should be maintained with the same degree of care one would expect for a
medical instrument sterilizer as the health risks with a malfunction in
either system would be similar and potentially lethal. Whether such a
certification course should evolve from the compressor manufacturers
themselves, an organization such as PSI, or a government agency would
need to be debated.
With a future fill station manager’s certification course hopefully
all those neglected dirty compressor systems kept in tiny, dank, and
excessively hot backrooms until now would finally be given the priority
and importance these ‘systems’ deserve. The diver’s breathing gas
compressor system is the most important piece of equipment in which one
must have full confidence, even ahead of all the other safety concerns
such as adequate training and gear quality. If not, then the first event
in that proverbial chain may often be contaminated gas despite having
the best equipment and hundreds of hours of training.
Next some pictures submitted by Barney of the
sampling process.